ANALISA EFISIENSI BOILER MITSUBISHI RADIAN REHEAT FORCED CIRCULATION BERDASARKAN PERFORMANCE TEST DENGAN METODE PERHITUNGAN HEAT LOSS PLTU TANJUNG JATI B UNIT B UNIT 4

TAMTOMO, ARDA AGAM (2019) ANALISA EFISIENSI BOILER MITSUBISHI RADIAN REHEAT FORCED CIRCULATION BERDASARKAN PERFORMANCE TEST DENGAN METODE PERHITUNGAN HEAT LOSS PLTU TANJUNG JATI B UNIT B UNIT 4. Skripsi thesis, Fakultas Teknik.

[img] Text
BAB II - IV.pdf
Restricted to Repository staff only

Download (1MB)
[img]
Preview
Text
BAB I & V.pdf

Download (4MB) | Preview

Abstract

Penelitian ini bertujuan untuk mengetahui nilai effisiensi boiler PLTU Tanjung Jati B unit 4 berdasarkan performance test. performance testmerupakan salah satu langkah untuk memastikan nilai effisiensi boiler masih dalam tahap yang aman.Berdasarkan ASME PTC 4.1, perhitungan nilai efisiensi boiler yang digunakan metode perhitungan heat losses (proses perhitungan rugi panas yang ada proses produksi uap). pengaruh total heat loss. terhadap efisiensi boiler nilainya berbanding lurus. Nilai efisiensi terendah pada bulan februari tahun 2014 adalah sebesar 87,6549 % dengan nilai losses total sebesar 12,3451 %. Kemudian untuk efisiensi tertinggi pada bulan Februari tahun 2013 adalah sebesar 88,1353 dengan nilai losses total sebesar 11,6204 %. Nilai losses pada efisiensi boiler adalah pada LG’ dengan nilai tertinggi sebesar 4,4779% pada bulan juli tahun 2013 dan nilai terendah dengan nilai 4,1858% pada Februari tahun 2013 dimana ini merupakan rugi panas yang terbawa gas buang kering, Performance test yang telah dilakukan mencapai nilai tertinggi LH adalah pada 4,2313% pada bulan Februari tahun 2014 dan nilai terendah adalah sebesar 4,0126% pada bulan Februari tahun 2013. // In this researh to determine the efficiency value of PLTU TanjungJati B unit 4 boilers based on performance tests. Performance test is one step to ensure the boiler efficiency value is still in a safe stage. Based on ASME PTC 4.1, the calculation of the value of the boiler efficiency used by the method of calculating heat losses (the process of calculating heat losses in the existing steam production process). influence of total heat loss. the value of boiler efficiency is directly proportional. The lowest efficiency value in February 2014 was 87.6549% with a total loss of 12.3451%. Then for the highest efficiency in February 2013 was 88,1353 with a total loss of 11.6204%. The value of losses in boiler efficiency is at LG 'with the highest value of 4.4779% in July 2013 and the lowest value with a value of 4.1858% in February 2013 where this is the heat loss carried by dry exhaust gases, Performance tests that have been achieved the highest LH value was 4.2313% in February 2014 and the lowest value was 4.0126% in February 2013

Item Type: Thesis (Skripsi)
Uncontrolled Keywords: Boiler, Effisiensi, Heat loos, Performance test, Boiler, Efficiency, Heat looses, Performance test
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Fakultas Teknik > Prodi Teknik Mesin
Depositing User: S.IP., MA Dwi Cahyo Prasetyo
Date Deposited: 06 Nov 2020 02:58
Last Modified: 06 Nov 2020 02:58
URI: http://repository.unmuhpnk.ac.id/id/eprint/1150

Actions (login required)

View Item View Item